János Vad, Eszter Lukács

Fluid Mechanics Measurements


Heat power measurement applied in a remote heating system

A remote heating system supplies hot water. The temperatures of the hot water supplied and the returning warm water are Tout and Tin, respectively. The water is supplied at a volume flow rate qV. The case study presented herein regards the measurement of heat power realised by the heating system, defined as presents in Eq. (8.12.1):

Fluid Mechanics Measurements

Tartalomjegyzék


Kiadó: Akadémiai Kiadó

Online megjelenés éve: 2020

ISBN: 978 963 454 484 5

This lecture note aims at providing basic information on nowadays applied fluid flow measurement techniques, in terms of their operating principle, layouts, application areas, advantages, and limitations. As such, it intends to give an aid in decision-making when selecting instrumentation for the solution of various practical flow measurement problems, also providing hints for the actual realisation of the measurements.